COMMISSION REGULATION (EU) 2015/1189 of 28 April 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for solid fuel boilers (Text with EEA relevance)

Article 1
Subject matter and scope

This Regulation shall not apply to:

(a) boilers generating heat exclusively for providing hot drinking or sanitary water;

(b) boilers for heating and distributing gaseous heat transfer media such as vapour or air;

(c) solid fuel cogeneration boilers with a maximum electrical capacity of 50 kW or more;

(d) non-woody biomass boilers.

Article 2
Definitions

In addition to the definitions set out in Article 2 of Directive 2009/125/EC, the following definitions shall apply for the purposes of this Regulation:

(1) ‘solid fuel boiler’ means a device equipped with one or more solid fuel heat generators that provides heat to a water-based central heating system in order to reach and maintain at a desired level the indoor temperature of one or more enclosed spaces, with a heat loss to its surrounding environment of not more than 6 % of rated heat output;

(2) ‘water-based central heating system’ means a system using water as a heat transfer medium to distribute centrally generated heat to heat emitting devices for the heating of enclosed spaces within buildings or parts thereof, including block heating or district heating networks;

(3) ‘solid fuel heat generator’ means the part of a solid fuel boiler that generates the heat through the combustion of solid fuels;

(4) ‘rated heat output’ or ‘Pr’ means the declared heat output of a solid fuel boiler when providing heating of enclosed spaces with the preferred fuel, expressed in kW;

(5) ‘solid fuel’ means a fuel that is solid at normal indoor room temperatures, including solid biomass and solid fossil fuel;

(6) ‘biomass’ means the biodegradable fraction of products, waste and residues from biological origin from agriculture (including vegetal and animal substances), forestry and related industries including fisheries and aquaculture, as well as the biodegradable fraction of industrial and municipal waste;

(7) ‘woody biomass’ means biomass originating from trees, bushes and shrubs, including log wood, chipped wood, compressed wood in the form of pellets, compressed wood in the form of briquettes, and sawdust;

(8) ‘non-woody biomass’ means biomass other than woody biomass, including straw, miscanthus, reeds, kernels, grains, olive stones, olive cakes and nut shells;

(9) ‘fossil fuel’ means fuel other than biomass, including anthracite, brown coal, coke, bituminous coal; for the purposes of this Regulation it also includes peat;

(10) ‘biomass boiler’ means a solid fuel boiler that uses biomass as the preferred fuel;

(11) ‘non-woody biomass boiler’ means a biomass boiler that uses non-woody biomass as the preferred fuel and for which woody biomass, fossil fuel or a blend of biomass and fossil fuel are not listed among its other suitable fuels;

(12) ‘preferred fuel’ means the single solid fuel which is to be preferably used for the boiler according to the manufacturer's instructions;

(13) ‘other suitable fuel’ means a solid fuel, other than the preferred fuel, which can be used in the solid fuel boiler according to the manufacturer's instructions and includes any fuel that is mentioned in the instruction manual for installers and end-users, on free access websites of manufacturers, in technical promotional material and in advertisements;

(14) ‘solid fuel cogeneration boiler’ means a solid fuel boiler capable of simultaneously generating heat and electricity;

(15) ‘seasonal space heating energy efficiency’ or ‘ηs’ means the ratio between the space heating demand for a designated heating season supplied by a solid fuel boiler and the annual energy consumption required to meet that demand, expressed in %;

(16) ‘particulate matter’ means particles of various shape, structure and density scattered in the gaseous phase of the flue gas.

For the purposes of Annexes II to V, additional definitions are set out in Annex I.

Article 3
Ecodesign requirements and timetable
Article 4
Conformity assessment
Article 5
Verification procedure for market surveillance purposes

Member States shall apply the verification procedure set out in Annex IV to this Regulation when performing the market surveillance checks referred to in Article 3(2) of Directive 2009/125/EC to ensure compliance with the requirements set out in Annex II to this Regulation.

Article 6
Indicative benchmarks

The indicative benchmarks for best-performing solid fuel boilers available on the market at the time of entry into force of this Regulation are set out in Annex V.

Article 7
Review

The Commission shall review this Regulation in the light of technological progress and present the result of that review to the Consultation Forum no later than 1 January 2022. In particular, the review shall assess whether it is appropriate:

(a) to include solid fuel boilers with a rated heat output of up to 1 000 kilowatt;

(b) to include non-woody biomass boilers, with ecodesign requirements for their specific types of pollutant emissions;

(c) to set stricter ecodesign requirements beyond 2020 for energy efficiency and for emissions of particulate matter, organic gaseous compounds and carbon monoxide; and

(d) to vary the verification tolerances.

Article 8
Transitional provision

Until 1 January 2020 Member States may allow the placing on the market and putting into service of solid fuel boilers which are in conformity with the national provisions in force regarding seasonal space heating energy efficiency, and emissions of particulate matter, organic gaseous compounds, carbon monoxide and nitrogen oxides.

Article 9
Entry into force

This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union.

This Regulation shall be binding in its entirety and directly applicable in all Member States.

ANNEX I

Definitions applicable to Annexes II to V

For the purposes of Annexes II to V the following definitions shall apply:

(1) ‘seasonal space heating emissions’ means: (a) for automatically stoked solid fuel boilers, a weighted average of the emissions at rated heat output and the emissions at 30 % of the rated heat output, expressed in mg/m3; (b) for manually stoked solid fuel boilers that can be operated at 50 % of the rated heat output in continuous mode, a weighted average of the emissions at rated heat output and the emissions at 50 % of the rated heat output, expressed in mg/m3; (c) for manually stoked solid fuel boilers that cannot be operated at 50 % or less of the rated heat output in continuous mode, the emissions at rated heat output, expressed in mg/m3; (d) for solid fuel cogeneration boilers, the emissions at rated heat output, expressed in mg/m3.

(2) ‘fossil fuel boiler’ means a solid fuel boiler that has fossil fuel or a blend of biomass and fossil fuel as preferred fuel;

(3) ‘solid fuel boiler housing’ means the part of a solid fuel boiler designed for fitting a solid fuel heat generator;

(4) ‘model identifier’ means the code, usually alphanumeric, which distinguishes a specific solid fuel boiler model from other models with the same trade mark or manufacturer's name;

(5) ‘condensing boiler’ means a solid fuel boiler in which, under normal operating conditions and at given operating water temperatures, the water vapour in the combustion products is partially condensed, in order to make use of the latent heat of this water vapour for heating purposes;

(6) ‘combination boiler’ means a solid fuel boiler that is designed to also provide heat to deliver hot drinking or sanitary water at given temperature levels, quantities and flow rates during given intervals, and is connected to an external supply of drinking or sanitary water;

(7) ‘other woody biomass’ means woody biomass other than: log wood with a moisture content of 25 % or less, chipped wood with a moisture content of 15 % or higher, compressed wood in the form of pellets or briquettes, or sawdust with a moisture content equal to or less than 50 %;

(8) ‘moisture content’ means the mass of water in the fuel in relation to the total mass of the fuel as used in solid fuel boilers;

(9) ‘other fossil fuel’ means fossil fuel other than bituminous coal, brown coal (including briquettes), coke, anthracite or blended fossil fuel briquettes;

(10) ‘electrical efficiency’ or ‘ηel’ means the ratio of the electricity output and the total energy input of a solid fuel cogeneration boiler, expressed in %, whereby the total energy input is expressed in terms of GCV or in terms of final energy multiplied by CC;

(11) ‘gross calorific value’ or ‘GCV’ means the total amount of heat released by a unit quantity of fuel containing the appropriate moisture content, when it is burned completely with oxygen, and when the products of combustion are returned to ambient temperature; this quantity includes the condensation heat of the water vapour formed by the combustion of any hydrogen contained in the fuel;

(12) ‘conversion coefficient’ or ‘CC’ means a coefficient reflecting the estimated 40 % average EU generation efficiency referred to in Directive 2012/27/EU of the European Parliament and of the Council (2); the value of the conversion coefficient is CC = 2,5;

(13) ‘electric power requirement at maximum heat output’ or ‘elmax’ means the electric power consumption of the solid fuel boiler at rated heat output, expressed in kW, excluding electricity consumption from a back-up heater and from incorporated secondary emission abatement equipment;

(14) ‘electric power requirement at minimum heat output’ or ‘elmin’ means the electric power consumption of the solid fuel boiler at applicable part load, expressed in kW, excluding electricity consumption from a back-up heater and from incorporated secondary emission abatement equipment;

(15) ‘back-up heater’ means a Joule-effect electric resistance element that generates heat only to prevent the solid fuel boiler or the water-based central heating system from freezing or when the external heat source supply is disrupted (including during maintenance periods) or out of order;

(16) ‘applicable part load’ means for automatically stoked solid fuel boilers, operation at 30 % of rated heat output, and for manually stoked solid fuel boilers that can be operated at 50 % of rated heat output, operation at 50 % of rated heat output;

(17) ‘standby mode power consumption’ or ‘PSB’ means the power consumption of a solid fuel boiler in standby mode, excluding from incorporated secondary emission abatement equipment, expressed in kW;

(18) ‘standby mode’ means a condition where the solid fuel boiler is connected to the mains power source, depends on energy input from the mains power source to work as intended and provides only the following functions, which may persist for an indefinite time: reactivation function, or reactivation function and only an indication of enabled reactivation function, or information or status display;

(19) ‘seasonal space heating energy efficiency in active mode’ or ‘ηson’ means: (a) for automatically stoked solid fuel boilers, a weighted average of the useful efficiency at rated heat output and the useful efficiency at 30 % of the rated heat output, expressed in %; (b) for manually stoked solid fuel boilers that can be operated at 50 % of the rated heat output in continuous mode, a weighted average of the useful efficiency at rated heat output and the useful efficiency at 50 % of the rated heat output, expressed in %; (c) for manually stoked solid fuel boilers that cannot be operated at 50 % or less of the rated heat output in continuous mode, the useful efficiency at rated heat output, expressed in %; (d) for solid fuel cogeneration boilers, the useful efficiency at rated heat output, expressed in %;

(20) ‘useful efficiency’ or ‘η’ means the ratio of the useful heat output and the total energy input of a solid fuel boiler, expressed in %, whereby the total energy input is expressed in terms of GCV or in terms of final energy multiplied by CC;

(21) ‘useful heat output’ or ‘P’ means the heat output of a solid fuel boiler transmitted to the heat carrier, expressed in kW;

(22) ‘temperature control’ means the equipment that interfaces with the end-user regarding the values and timing of the desired indoor temperature, and communicates relevant data to an interface of the solid fuel boiler such as a central processing unit, thus helping to regulate the indoor temperature(s);

(23) ‘gross calorific value moisture free’ or ‘GCVmf’ means the total amount of heat released by a unit quantity of fuel dried of inherent moisture, when it is burned completely with oxygen, and when the products of combustion are returned to ambient temperature; this quantity includes the condensation heat of the water vapour formed by the combustion of any hydrogen contained in the fuel;

(24) ‘equivalent model’ means a model placed on the market with the same technical parameters set out in Table 1 of point 2 of Annex II as another model placed on the market by the same manufacturer.

ANNEX II

Ecodesign requirements

1. Specific ecodesign requirements

From 1 January 2020 solid fuel boilers shall comply with the following requirements:

(a) seasonal space heating energy efficiency for boilers with a rated heat output of 20 kW or less shall not be less than 75 %;

(b) seasonal space heating energy efficiency for boilers with a rated heat output of more than 20 kW shall not be less than 77 %;

(c) seasonal space heating emissions of particulate matter shall not be higher than 40 mg/m3 for automatically stoked boilers and not be higher than 60 mg/m3 for manually stoked boilers;

(d) seasonal space heating emissions of organic gaseous compounds shall not be higher than 20 mg/m3 for automatically stoked boilers and not be higher than 30 mg/m3 for manually stoked boilers;

(e) seasonal space heating emissions of carbon monoxide shall not be higher than 500 mg/m3 for automatically stoked boilers and not be higher than 700 mg/m3 for manually stoked boilers;

(f) seasonal space heating emissions of nitrogen oxides, expressed in nitrogen dioxide, shall not be higher than 200 mg/m3 for biomass boilers and not be higher than 350 mg/m3 for fossil fuel boilers;

These requirements shall be met for the preferred fuel and for any other suitable fuel for the solid fuel boiler.

2. Requirements for product information

From 1 January 2020 the following product information on solid fuel boilers shall be provided:

(a) in the instruction manuals for installers and end-users, and on the free-access websites of manufacturers, their authorised representatives and importers: (1) the information included in Table 1, with its technical parameters measured and calculated in accordance with Annex III and showing the number of significant figures indicated in the table; (2) any specific precautions to be taken when the solid fuel boiler is assembled, installed or maintained; (3) instruction on the proper way to operate the solid fuel boiler and on the quality requirements for the preferred fuel and any other suitable fuels; (4) for solid fuel heat generators designed for solid fuel boilers, and solid fuel boiler housings to be equipped with such heat generators, their characteristics, the requirements for assembly (to ensure compliance with the ecodesign requirements for solid fuel boilers) and, where appropriate, the list of combinations recommended by the manufacturer;

(b) on a part for professionals of the free-access websites of manufacturers, their authorised representatives and importers: information relevant to disassembly, recycling and disposal at end-of-life;

(c) in the technical documentation for the purposes of conformity assessment pursuant to Article 4: (1) the information listed in points (a) and (b); (2) a list of all equivalent models, if applicable; (3) where the preferred fuel or any other suitable fuel is other woody biomass, non-woody biomass, other fossil fuel or other blend of biomass and fossil fuel as referred to in Table 1, a description of the fuel sufficient for its unambiguous identification and the technical standard or specification of the fuel, including the measured moisture content, and the measured ash content, and for other fossil fuel also the measured volatile content of the fuel;

(d) the electrical capacity, marked in a permanent manner on the solid fuel cogeneration boiler.

The information referred to in point (c) may be merged with the technical documentation provided in accordance with measures under Directive 2010/30/EU.

Model identifier(s)
Stoking mode: [Manual: the boiler should be operated with a hot water storage tank of a volume of at least x (1) litre/Automatic: it is recommended that the boiler be operated with a hot water storage tank of a volume of at least x (2) litre]
Condensing boiler: [yes/no]
Solid fuel cogeneration boiler: [yes/no] Combination boiler: [yes/no]
Fuel Preferred fuel (only one): Other suitable fuel(s): ηs [x%]: Seasonal space heating emissions (*4)
PM OGC CO NOx
[x] mg/m3
Log wood, moisture content ≤ 25 % [yes/no] [yes/no]
Chipped wood, moisture content 15-35 % [yes/no] [yes/no]
Chipped wood, moisture content > 35 % [yes/no] [yes/no]
Compressed wood in the form of pellets or briquettes [yes/no] [yes/no]
Sawdust, moisture content ≤ 50 % [yes/no] [yes/no]
Other woody biomass [yes/no] [yes/no]
Non-woody biomass [yes/no] [yes/no]
Bituminous coal [yes/no] [yes/no]
Brown coal (including briquettes) [yes/no] [yes/no]
Coke [yes/no] [yes/no]
Anthracite [yes/no] [yes/no]
Blended fossil fuel briquettes [yes/no] [yes/no]
Other fossil fuel [yes/no] [yes/no]
Blended biomass (30-70 %)/fossil fuel briquettes [yes/no] [yes/no]
Other blend of biomass and fossil fuel [yes/no] [yes/no]
Characteristics when operating with the preferred fuel only:
Item Symbol Value Unit Item Symbol Value Unit
Useful heat output Useful efficiency
At rated heat output Pn (*3) x,x kW At rated heat output ηn x,x %
At [30 %/50 %] of rated heat output, if applicable Pp [x,x/N.A.] kW At [30 %/50 %] of rated heat output, if applicable ηp [x,x/N.A.] %
For solid fuel cogeneration boilers: Electrical efficiency Auxiliary electricity consumption
At rated heat output elmax x,xxx kW
At rated heat output ηel,n x,x % At [30 %/50 %] of rated heat output, if applicable elmin [x,xxx/N.A.] kW
Of incorporated secondary emission abatement equipment, if applicable [x,xxx/N.A.] kW
In standby mode PSB x,xxx kW
Contact details Name and address of the manufacturer or its authorised representative.
(1) Tank volume = 45 × Pr × (1 – 2,7/Pr) or 300 litres, whichever is higher, with Pr indicated in kW (2) Tank volume = 20 × Pr with Pr indicated in kW (3) For the preferred fuel Pn equals Pr (4) PM = particulate matter, OGC = organic gaseous compounds, CO = carbon monoxide, NOx = nitrogen oxides

ANNEX III

Measurements and calculations

1.

For the purposes of compliance and verification of compliance with the requirements of this Regulation, measurements and calculations shall be made using harmonised standards the reference numbers of which have been published for this purpose in the Official Journal of the European Union, or using other reliable, accurate and reproducible methods that take into account the generally recognised state-of-the-art methods. They shall meet the conditions and technical parameters set out in points 2 to 6.

5.

The gross calorific value (GCV) shall be obtained from the gross calorific value moisture free (GCVmf) by applying the following conversion:

GCV = GCVmf × (1 – M) where:

ANNEX IV

Product compliance verification by market surveillance authorities

The verification tolerances defined in this Annex relate only to the verification of the measured parameters by Member State authorities and shall not be used by the manufacturer or importer as an allowed tolerance to establish the values in the technical documentation or in interpreting these values with a view to achieving compliance or to communicate better performance by any means.

When verifying the compliance of a product model with the requirements laid down in this Regulation pursuant to Article 3(2) of Directive 2009/125/EC, for the requirements referred to in this Annex, the authorities of the Member States shall apply the following procedure:

(1) The Member State authorities shall verify one single unit of the model.

(2) The model shall be considered to comply with the applicable requirements if: (a) the values given in the technical documentation pursuant to point 2 of Annex IV to Directive 2009/125/EC (declared values), and, where applicable, the values used to calculate these values, are not more favourable for the manufacturer or importer than the results of the corresponding measurements carried out pursuant to paragraph (g) thereof; and (b) the declared values meet any requirements laid down in this Regulation, and any required product information published by the manufacturer or importer does not contain values that are more favourable for the manufacturer or importer than the declared values; and (c) when the Member State authorities test the unit of the model, the determined values (the values of the relevant parameters as measured in testing and the values calculated from these measurements) comply with the respective verification tolerances as given in Table 2. The unit shall be tested with one or more fuels with characteristics in the same range as the fuel(s) that were used by the manufacturer to perform the measurements described in Annex III.

(3) If the results referred to in point 2(a) or (b) are not achieved, the model and all models that have been listed as equivalent models in the manufacturer's or importer's technical documentation shall be considered not to comply with this Regulation.

(4) If the result referred to in point 2(c) is not achieved, the Member State authorities shall select three additional units of the same model for testing. As an alternative, the three additional units selected may be of one or more different models that have been listed as equivalent models in the manufacturer's or importer's technical documentation.

(5) The model shall be considered to comply with the applicable requirements if, for these three units, the arithmetical mean of the determined values complies with the respective verification tolerances given in Table 2.

(6) If the result referred to in point 5 is not achieved, the model and all models that have been listed as equivalent models in the manufacturer's or importer's technical documentation shall be considered not to comply with this Regulation.

(7) The Member State authorities shall provide all relevant information to the authorities of the other Member States and to the Commission without delay after a decision being taken on the non-compliance of the model according to points 3 and 6.

The Member State authorities shall use the measurement and calculation methods set out in Annex III.

The Member State authorities shall only apply the verification tolerances that are set out in Table 2 and shall only use the procedure described in points 1 to 7 for the requirements referred to in this Annex. No other tolerances, such as those set out in harmonised standards or in any other measurement method, shall be applied.

Parameters Verification tolerance
Seasonal space-heating energy efficiency, ηs The determined value shall not be lower than the declared value by more than 4 %.
Emissions of particulate matter The determined value shall not exceed the declared value by more than 9 mg/m3.
Emissions of organic gaseous compounds The determined value shall not exceed the declared value by more than 7 mg/m3.
Emissions of carbon monoxide The determined value shall not exceed the declared value by more than 30 mg/m3.
Emissions of nitrogen oxides The determined value shall not exceed the declared value by more than 30 mg/m3.

ANNEX V

Indicative benchmarks referred to in Article 6

The indicative benchmarks for the best available technology on the market for solid fuel boilers at the time of entry into force of this Regulation are as follows. At the time of entry into force of this Regulation, no single solid fuel boiler was identified meeting all the values specified in points 1 and 2. Several solid fuel boilers met one or more of these values:

1.

For seasonal space heating energy efficiency: 96 % for solid fuel cogeneration boilers, 90 % for condensing boilers and 84 % for other solid fuel boilers.

2.

For seasonal space heating emissions:

(a) 2 mg/m3 for particulate matter for biomass boilers; 10 mg/m3 for fossil fuel boilers; (b) 1 mg/m3 for organic gaseous compounds; (c) 6 mg/m3 for carbon monoxide; (d) 97 mg/m3 for nitrogen oxides for biomass boilers; 170 mg/m3 for fossil fuel boilers.

The benchmarks specified in points 1 and 2(a) to (d) do not necessarily imply that a combination of those values is achievable for a single solid fuel boiler. An example of a good combination is an existing model with a seasonal space heating energy efficiency of 81 % and seasonal space heating emissions of particulate matter of 7 mg/m3, of organic gaseous compounds of 2 mg/m3, of carbon monoxide of 6 mg/m3 and of nitrogen oxides of 120 mg/m3.

Reading this document does not replace reading the official text published in the Official Journal of the European Union. We assume no responsibility for any inaccuracies arising from the conversion of the original to this format.

This text is published under EUR-Lex's own terms of reuse, not a Legalize or public-domain licence. EUR-Lex
Creative Commons Attribution 4.0 International (CC BY 4.0)
© European Union, https://eur-lex.europa.eu — Source: EUR-Lex (Publications Office of the European Union). Reused under the Creative Commons Attribution 4.0 International (CC BY 4.0) licence. Only EU legislation published in the printed Official Journal of the European Union is deemed authentic; consolidated texts are reproduced here for documentation purposes and have been reformatted to Markdown.