| 2.2.3.1. | In addition to complying with the specific provisions for fire integrity of bulkheads and decks mentioned elsewhere in this part, the minimum fire integrity of all bulkheads and decks shall be as prescribed in tables 9.1 and 9.2. | |
| --- | --- | --- |
| 2.2.3.2. | The following requirements shall govern the application of the tables: .1 Table 9.1 shall apply to bulkheads not bounding either main vertical zones or horizontal zones. Table 9.2 shall apply to decks not forming steps in main vertical zones nor bounding horizontal zones. .2 For determining the appropriate fire integrity standards to be applied to boundaries between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (14). Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this Regulation II-2/C/9, it shall be treated as a space within the relevant category having the most stringent boundary requirements. The title of each category is intended to be typical rather than restrictive. The number in parentheses preceding each category refers to the applicable column or row in the tables. (1) Control stations: — spaces containing emergency sources of power and lighting, — wheelhouse and chartroom, — spaces containing the ship’s radio equipment, — fire-extinguishing rooms, fire control rooms and fire-recording stations, — control room for propulsion machinery when located outside the propulsion machinery space, — spaces containing centralised fire alarm equipment, — spaces containing centralised emergency public address system stations and equipment. (2) Stairways: — interior stairways, lifts and escalators (other than those wholly contained within the machinery spaces) for passengers and crew and enclosures thereto; — in this connection a stairway which is enclosed at only one level shall be regarded as part of the space from which it is not separated by a fire door. (3) Corridors: — passenger and crew corridors. (4) Evacuation stations and external escape routes: — survival craft stowage area, — open deck spaces and enclosed promenades forming lifeboat and life-raft embarkation and lowering stations, — assembly stations, internal and external, — external stairs and open decks used for escape routes, — the ship’s side to the waterline in the lightest seagoing condition, superstructure and deckhouse sides situated below and adjacent to the life-rafts and evacuation slide’s embarkation areas. (5) Open deck spaces: — open deck spaces and enclosed promenades clear of lifeboat and life-raft embarkation and lowering stations, — air spaces (the space outside superstructures and deckhouses). (6) Accommodation spaces of minor fire risk: — cabins containing furniture and furnishing of restricted fire risk, — offices and dispensaries containing furniture and furnishings of restricted fire risk, — public spaces containing furniture and furnishings of restricted fire risk and having a deck area of less than 50 m2. (7) Accommodation spaces of moderate fire risk: — spaces as in category (6) above but containing furniture and furnishing of other than restricted fire risk, — public spaces containing furniture and furnishing of restricted fire risk and having a deck area of 50 m2 or more, — isolated lockers and small storerooms in accommodation spaces having areas less than 4 m2 (in which flammable liquids are not stowed), — sale shops, — motion picture projection and film stowage rooms, — diet kitchens (containing no open flame), — cleaning gear lockers (in which flammable liquids are not stowed), — laboratories (in which flammable liquids are not stowed), — pharmacies, — small drying rooms (having a deck area of 4 m2 or less), — specie rooms, — operating rooms. (8) Accommodation spaces of greater fire risk: — public spaces containing furniture and furnishing of other than restricted fire risk and having a deck area of 50 m2 or more, — barber shops and beauty parlours, — saunas, — sale shops. (9) Sanitary and similar spaces: — communal sanitary facilities, shower, baths, water closets, etc., — small laundry rooms, — indoor swimming pool area, — isolated pantries containing no cooking appliances in accommodation spaces, — private sanitary facilities shall be considered a portion of the space in which they are located. (10) Tanks, voids and auxiliary machinery spaces having little or no fire risk: — water tanks forming part of the ship’s structure; — voids and cofferdams; — auxiliary machinery spaces which do not contain machinery having a pressure lubrication system and where storage of combustibles is prohibited, such as: — ventilation and air-conditioning rooms; windlass room; steering gear room; stabiliser equipment room; electrical propulsion motor room; rooms containing section switchboards and purely electrical equipment other than oil-filled electrical transformers (above 10 kVA); shaft alleys and pipe tunnels; spaces for pumps and refrigeration machinery (not handling or using flammable liquids), — closed trunks serving the spaces listed above, — other closed trunks such as pipe and cable trunks. (11) Auxiliary machinery spaces, cargo spaces, cargo and other oil tanks and other similar spaces of moderate fire risk: — cargo oil tanks, — cargo holds, trunkways and hatchways, — refrigerated chambers, — oil fuel tanks (where installed in a separate space with no machinery), — shaft alleys and pipe tunnels allowing storage of combustibles, — auxiliary machinery spaces as in category (10) which contain machinery having a pressure lubrication system or where storage of combustibles is permitted, — oil fuel filling stations, — spaces containing oil-filled electrical transformers (above 10 kVA), — spaces containing small internal combustion engines of power output up to 110 kW driving generators, sprinkler, drencher or fire pumps, bilge pumps, etc., — closed trunks serving the spaces listed above. (12) Machinery spaces and main galleys: — main propulsion machinery rooms (other than electric propulsion motor rooms) and boiler rooms, — auxiliary machinery spaces other than those in categories (10) and (11) which contain internal combustion machinery or other oil burning, heating or pumping units, — main galleys and annexes, — trunks and casings to the spaces listed above. (13) Store-rooms, workshops, pantries, etc.: — main pantries not annexed to galleys, — main laundry, — large drying rooms (having a deck area of more than 4 m2), — miscellaneous stores, — mail and baggage rooms, — garbage rooms, — workshops (not part of machinery spaces, galleys, etc.), — lockers and storerooms having areas greater than 4 m2, other than those spaces that have provisions for the storage of flammable liquids. (14) Other spaces in which flammable liquids are stowed: — paint lockers, — store-rooms containing flammable liquids (including dyes, medicines, etc.), — laboratories (in which flammable liquids are stowed). .3 Where a single value is shown for the fire integrity of a boundary between two spaces, that value shall apply in all cases. .4 There are no special requirements for material or integrity of boundaries where only a dash appears in the tables. .5 The Administration of the flag State shall determine in respect of category (5) spaces whether the insulation values in table 9.1 shall apply to ends of deckhouses and superstructures, and whether the insulation values in table 9.2 shall apply to weather decks. In no case shall the requirements of category (5) of tables 9.1 or 9.2 necessitate enclosure of spaces which in the opinion of the Administration of the flag State need not be enclosed. | |
| --- | --- | --- |
| 2.2.3.3. | Continuous ‘B’ class ceiling or linings, in association with the relevant decks or bulkheads, may be accepted as contributing wholly or in part, to the required insulation and integrity of a division. | |
| --- | --- | --- |
| 2.2.3.4. | Construction and arrangement of saunas | |
| --- | --- | --- |
| 2.2.3.4.1 | The perimeter of the sauna shall be of "A" class boundaries and may include changing rooms, showers and toilets. The sauna shall be insulated to A-60 standard against other spaces except those inside of the perimeter and spaces of categories (5), (9) and (10). | |
| --- | --- | --- |
| 2.2.3.4.2 | Bathrooms with direct access to saunas may be considered as part of them. In such cases, the door between sauna and the bathroom need not comply with fire safety requirements. | |
| --- | --- | --- |
| 2.2.3.4.3 | The traditional wooden lining on the bulkheads and ceiling are permitted in the sauna. The ceiling above the oven shall be lined with a non-combustible plate with an air gap of at least 30 mm. The distance from the hot surfaces to combustible materials shall be at least 500 mm or the combustible materials shall be protected (e.g. non-combustible plate with an air gap of at least 30 mm). | |
| --- | --- | --- |
| 2.2.3.4.4 | The traditional wooden benches are permitted to be used in the sauna. | |
| --- | --- | --- |
| 2.2.3.4.5 | The sauna door shall open outwards by pushing. | |
| --- | --- | --- |
| 2.2.3.4.6 | Electrically heated ovens shall be provided with a timer. Table 9.1 Bulkheads not bounding either main vertical zones or horizontal zones Spaces (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) Control stations (1) B-0 (a) A-0 A-0 A-0 A-0 A-60 A-60 A-60 A-0 A-0 A-60 A-60 A-60 A-60 Stairways (2) A-0 (a) A-0 A-0 A-0 A-0 A-15 A-15 A-0 (c) A-0 A-15 A-30 A-15 A-30 Corridors (3) B-15 A-60 A-0 B-15 B-15 B-15 B-15 A-0 A-15 A-30 A-0 A-30 Evacuation stations and external escape routes (4) A-0 A-60 (b,d) A-60 (b,d) A-60 (b,d) A-0 (d) A-0 A-60 (b) A-60 (b) A-60 (b) A-60 (b) Open deck spaces (5) — A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 Accommodation spaces of minor fire risk (6) B-0 B-0 B-0 C A-0 A-0 A-30 A-0 A-30 Accommodation spaces of moderate fire risk (7) B-0 B-0 C A-0 A-15 A-60 A-15 A-60 Accommodation spaces of greater fire risk (8) B-0 C A-0 A-30 A-60 A-15 A-60 Sanitary and similar spaces (9) C A-0 A-0 A-0 A-0 A-0 Tanks, voids and auxiliary machinery spaces having little or no fire risk (10) A-0 (a) A-0 A-0 A-0 A-0 Auxiliary machinery spaces, cargo spaces, cargo and other oil tanks and other similar spaces of moderate fire risk (11) A-0 (a) A-0 A-0 A-15 Machinery spaces and main galleys (12) A-0 (a) A-0 A-60 Storerooms, workshops, pantries, etc. (13) A-0 (a) A-0 Other spaces in which flammable liquids are stowed (14) A-30 Table 9.2 Decks neither forming steps in main vertical zones nor bounding horizontal zones Space below↓ Space above→ (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) Control stations (1) A-30 A-30 A-15 A-0 A-0 A-0 A-15 A-30 A-0 A-0 A-0 A-60 A-0 A-60 Stairways (2) A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-30 A-0 A-30 Corridors (3) A-15 A-0 A-0 (a) A-60 A-0 A-0 A-15 A-15 A-0 A-0 A-0 A-30 A-0 A-30 Evacuation stations and external escape routes (4) A-0 A-0 A-0 A-0 — A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 Open deck spaces (5) A-0 A-0 A-0 A-0 — A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 Accommodation spaces of minor fire risk (6) A-60 A-15 A-0 A-60 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 Accommodation spaces of moderate fire risk (7) A-60 A-15 A-15 A-60 A-0 A-0 A-15 A-15 A-0 A-0 A-0 A-0 A-0 A-0 Accommodation spaces of greater fire risk (8) A-60 A-15 A-15 A-60 A-0 A-15 A-15 A-30 A-0 A-0 A-0 A-0 A-0 A-0 Sanitary and similar spaces (9) A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 Tanks, voids and auxiliary machinery spaces having little or no fire risk (10) A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 A-0 (a) A-0 A-0 A-0 A-0 Auxiliary machinery spaces, cargo spaces, cargo and other oil tanks and other similar spaces of moderate fire risk (11) A-60 A-60 A-60 A-60 A-0 A-0 A-15 A-30 A-0 A-0 A-0 (a) A-0 A-0 A-30 Machinery spaces and main galleys (12) A-60 A-60 A-60 A-60 A-0 A-60 A-60 A-60 A-0 A-0 A-30 A-30 (a) A-0 A-60 Storerooms, workshops, pantries, etc. (13) A-60 A-30 A-15 A-60 A-0 A-15 A-30 A-30 A-0 A-0 A-0 A-0 A-0 A-0 Other spaces in which flammable liquids are stowed (14) A-60 A-60 A-60 A-60 A-0 A-30 A-60 A-60 A-0 A-0 A-0 A-0 A-0 A-0 Notes to be applied to tables 9.1 and 9.2 (a) Where adjacent spaces are in the same numerical category and superscript ‘a’ appears, a bulkhead or deck between such spaces need not to be fitted if deemed unnecessary by the Administration of the flag State. For example, in category (12) a bulkhead need not be required between a galley and its annexed pantries provided the pantry bulkhead and decks maintain the integrity of the galley boundaries. A bulkhead is, however, required between a galley and a machinery space even though both spaces are in category (12). (b) The ship’s side, to the waterline in the lightest seagoing condition, superstructure and deckhouse sides situated below and adjacent to the life-rafts and evacuation slides may be reduced to ‘A-30’. (c) Where public toilets are installed completely within the stairway enclosure, the public toilet bulkhead within the stairway enclosure can be of ‘B’ class integrity. (d) Where spaces of categories (6), (7), (8) and (9) are located completely within the outer perimeter of the assembly station, the bulkheads of these spaces are allowed to be of ‘B-0’ class integrity. Control positions for audio, video and light installations may be considered as part of the assembly station. Additional general notes to table 9.1 when applied to vertical divisions made of aluminium 1. As a general rule both sides should be insulated to the standard indicated in table 9.1. 2. In boundaries where one of the sides is facing spaces category (5), (6), (9) or (10) and the other side is facing spaces of any other category different from those, only the side facing the latter space should be insulated according to the standard indicated in table 9.1. 3. In boundaries where both spaces are included in categories (5), (6), (9) or (10), the following criteria should be followed: i. Open deck (5)/Accommodation Space of minor fire risk (6) - The insulation shall be installed facing only the accommodation space. ii. Open deck (5)/Sanitary Space (9) - The insulation shall be installed facing only the sanitary space. iii. Open deck (5)/Tanks, voids and auxiliary machinery spaces having little or no fire risk (10) - The insulation shall be installed facing only space (10). However, when space (10) is a tank or a void space, no insulation needs to be installed on either side. iv. Accommodation space of minor fire risk (6)/Sanitary Space (9) - the table 9.1 indicates a C standard between those two spaces. Accordingly, there is no insulation needed on either side. v. Accommodation space of minor fire risk (6)/Tanks, voids and auxiliary machinery spaces having little or no fire risk (10) - the insulation shall be installed facing only the accommodation space. vi. Sanitary Space (9)/Tanks, voids and auxiliary machinery spaces having little or no fire risk (10) - the insulation shall be installed facing only the sanitary space unless the category (10) space is an auxiliary machinery space having little or no fire risk, in which case the insultation shall be installed facing only the category (10) space. vii. The side shell within spaces of category different than (5), (6), (9) or (10) will be insulated up to the bulkhead deck according to the standard indicated in table 9.1, assuming that the adjacent space is category (5). Additional general notes to table 9.2 when applied to horizontal divisions made of aluminium 1. As a general rule both sides should be insulated to the standard indicated in table 9.2. 2. In boundaries where one of the sides is facing spaces category (5), (6), (9) and (10) and the other side is facing spaces of any other category different from those, only the side facing the latter space should be insulated according to the standard indicated in table 9.2. 3. In boundaries where both spaces are included in categories (5), (6), (9) or (10), the insulation shall be only installed underside. 4. Where the space above in the boundary is provided with fixed fire-fighting installation, the insulation needs only to be provided on the underside of the division, with the exception of special category and ro-ro cargo spaces. |
2.2.4. Fire integrity of bulkheads and decks in ships carrying not more than 36 passengers
| 2.2.4.1. | In addition to complying with the specific provisions for fire integrity of bulkheads and decks mentioned elsewhere in this part, the minimum fire integrity of bulkheads and decks shall be as prescribed in tables 9.3 and 9.4, as appropriate. | |
| --- | --- | --- |
| 2.2.4.2. | The following requirements shall govern application of the tables: .1 Tables 9.3 and 9.4 shall apply respectively to the bulkheads and decks separating adjacent spaces. .2 For determining the appropriate fire integrity standards to be applied to divisions between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (11) below. Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this Regulation II-2/C/9, it shall be treated as a space within the relevant category having the most stringent boundary requirements. The title of each category is intended to be typical rather than restrictive. The number in parentheses preceding each category refers to the applicable column or row in the tables. (1) Control stations: — spaces containing emergency sources of power and lighting, — wheelhouse and chartroom, — spaces containing the ship’s radio equipment, — fire-extinguishing rooms, fire control rooms and fire-recording stations, — control room for propulsion machinery when located outside the propulsion machinery space, — spaces containing centralised fire alarm equipment. (2) Corridors: — passenger and crew corridors and lobbies. (3) Accommodation spaces: — spaces as defined in Regulation II-2/A/3, paragraph 1 excluding corridors. (4) Stairways: — interior stairways, lifts and escalators (other than those wholly contained within the machinery spaces) and enclosures thereto, — in this connection, a stairway which is enclosed only at one level shall be regarded as part of the space from which it is not separated by a fire door. (5) Service spaces (low risk): — lockers and storerooms not having provisions for the storage of flammable liquids and having areas less than 4 m2 and drying rooms and laundries. (6) Machinery spaces of category A: — spaces as defined in Regulation II-2/A/3, paragraph 31. (7) Other machinery spaces: — spaces as defined in Regulation II-2/A/3, paragraph 30, excluding machinery spaces of category A. (8) Cargo spaces: — all spaces used for cargo (including cargo oil tanks) and trunkways and hatchways to such spaces, other than special category spaces. (9) Service spaces (high risk): — galleys, pantries containing cooking appliances, paint and lamp rooms, lockers and storerooms having areas of 4 m2 or more, spaces for the storage of flammable liquids, saunas and workshops other than those forming part of the machinery spaces. (10) Open decks: — open deck spaces and enclosed promenades having no fire risk. Air spaces (the space outside superstructures and deckhouses). (11) Special category and ro-ro cargo spaces: — spaces as defined in Regulation II-2/A/3, paragraphs 41 and 46. .3 In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is not protected by an automatic sprinkler system complying with the provisions of Regulation II-2/C/10, subparagraph 6.1.100 or between such zones neither of which is so protected, the higher of the two values given in the tables shall apply. .4 In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is protected by an automatic sprinkler system complying with the provisions of Regulation II-2/C/10, subparagraph 6.1.100 or between such zones both of which are so protected, the lesser of the two values given in the tables shall apply. Where a sprinklered zone and a non-sprinklered zone meet within accommodation and service spaces, the higher of the two values given in the tables shall apply to the division between the zones. | |
| --- | --- | --- |
| 2.2.4.3. | Continuous ‘B’ class ceilings or linings, in association with the relevant decks or bulkheads, may be accepted as contributing, wholly or in part, to the required insulation and integrity of a division. | |
| --- | --- | --- |
| 2.2.4.4. | External boundaries which are required in Regulation II-2/C/11, paragraph 2 to be of steel or other equivalent material may be pierced for the fitting of windows and sidescuttles provided that there is no requirement for such boundaries to have ‘A’ class integrity elsewhere in this part. Similarly, in such boundaries which are not required to have ‘A’ class integrity, doors may be of materials to the satisfaction of the Administration of the flag State. | |
| --- | --- | --- |
| 2.2.4.5. | Saunas shall comply with paragraph 2.2.3.4. Table 9.3 Fire integrity of bulkheads separating adjacent spaces Spaces (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) Control stations (1) A-0 (c) A-0 A-60 A-0 A-15 A-60 A-15 A-60 A-60 () A-60 Corridors (2) C (e) B-0(e) A-0 (a) B-0(e) A-60 A-0 A-0 A-15 () A-30 B-0 (e) A-0 (d) Accommodation spaces (3) C (e) A-0 (a) B-0 (e) A-60 A-0 A-0 A-15 () A-30 B-0 (e) A-0 (d) A-0 (d) Stairways (4) A-0 (a) A-0 (a) A-60 A-0 A-0 A-15 () A-30 B-0 (e) B-0 (e) A-0 (d) Service spaces (low risk) (5) C (e) A-60 A-0 A-0 A-0 () A-0 Machinery spaces of category A (6) () A-0 A-0 A-60 () A-60 Other machinery spaces (7) A-0 (b) A-0 A-0 () A-0 Cargo spaces (8) () A-0 () A-0 Service spaces (high risk) (9) A-0 (b) () A-30 Open decks (10) A-0 Special category and ro-ro cargo spaces (11) A-30 Table 9.4 Fire integrity of decks separating adjacent spaces Space below↓ Space above→ (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) Control stations (1) A-0 A-0 A-0 A-0 A-0 A-60 A-0 A-0 A-0 () A-30 Corridors (2) A-0 () () A-0 () A-60 A-0 A-0 A-0 () A-0 Accommodation spaces (3) A-60 A-0 () A-0 () A-60 A-0 A-0 A-0 () A-30 A-0 (d) Stairways (4) A-0 A-0 A-0 () A-0 A-60 A-0 A-0 A-0 () A-0 Service spaces (low risk) (5) A-15 A-0 A-0 A-0 () A-60 A-0 A-0 A-0 () A-0 Machinery spaces of category A (6) A-60 A-60 A-60 A-60 A-60 () A-60 (f) A-30 A-60 () A-60 Other machinery spaces (7) A-15 A-0 A-0 A-0 A-0 A-0 () A-0 A-0 () A-0 Cargo spaces (8) A-60 A-0 A-0 A-0 A-0 A-0 A-0 () A-0 () A-0 Service spaces (high risk) (9) A-60 A-30 A-30 A-30 A-0 A-60 A-0 A-0 A-0 () A-30 A-0 (d) A-0 (d) A-0 (d) Open decks (10) () () () () () () () () () — A-0 Special category and ro-ro cargo spaces (11) A-60 A-30 A-30 A-30 A-0 A-60 A-0 A-0 A-30 A-0 A-30 A-0 (d) Notes to be applied to both tables 9.3 and 9.4, as appropriate. (a) For clarification as to which applies, see paragraphs 2.2.2 and 2.2.5. (b) Where spaces are of the same numerical category and superscript ‘b’ appears, a bulkhead or deck of the rating shown in the tables is only required when the adjacent spaces are for a different purpose, e.g. in category (9). A galley next to a galley does not require a bulkhead but a galley next to a paint room requires an ‘A-0’ bulkhead. (c) Bulkheads separating the wheelhouse and chartroom from each other may be ‘B-0’ rating. (d) See paragraphs 2.2.4.2.3 and 2.2.4.2.4 of this Regulation II-2/C/9. (e) For the application of paragraph 2.2.1.1.2, ‘B-0’ and ‘C’, where appearing in table 9.3, shall be read as ‘A-0’. (f) Fire insulation need not be fitted if the machinery space in category (7) has little or no fire risk. () Where an asterisk appears in the tables, the division is required to be of steel or other equivalent material but is not required to be of ‘A’ class standard. However, where a deck, except in a category (10) space, is penetrated for the passage of electric cables, pipes and ventilation ducts, such penetration shall be made tight to prevent the passage of flame and smoke. Divisions between control stations (emergency generators) and open decks may have air intake openings without means for closure, unless a fixed gas fire-fighting system is fitted. For the application of paragraph 2.2.1.1.2. an asterisk, where appearing in table 9.4, except for categories (8) and (10), shall be read as ‘A-0’. Additional general notes to table 9.3 when applied to vertical divisions made of aluminium 1. As a general rule both sides should be insulated to the standard indicated in table 9.3. 2. In boundaries where one of the sides is facing spaces category (5) or (10) and the other side is facing spaces of any other category different from those, only the side facing the latter space should be insulated according to the standard indicated in table 9.3. Additional general notes to table 9.4 when applied to horizontal divisions made of aluminium 1. As a general rule both sides should be insulated to the standard indicated in table 9.4. 2. In boundaries where one of the sides is facing spaces category (5) and (10) and the other side is facing spaces of any other category different from those, only the side facing the latter space should be insulated according to the standard indicated in table 9.4. 3. Where the space above in the boundary is provided with fixed fire-fighting installation, the insulation needs only to be provided on the underside of the division, with the exception of special category and ro-ro cargo spaces. |
2.2.5. Protection of stairways and lifts in accommodation and service spaces
| 2.2.5.1. | All stairways shall be within enclosures formed of ‘A’ class divisions, with positive means of closure of all openings except that: .1 a stairway connecting only two decks need not be enclosed, provided the integrity of the deck is maintained by proper bulkheads or doors in one between-deck space. When a stairway is closed in one between-deck space, the stairway enclosure shall be protected in accordance with the tables for decks in paragraphs 2.2.3 and 2.2.4; .2 stairways may be fitted in the open in a public space, provided they lie wholly within such public space. | |
| --- | --- | --- |
| 2.2.5.2. | Lift trunks shall be so fitted as to prevent the passage of smoke and flame from one between-deck to another and shall be provided with means of closing so as to permit the control of draught and smoke. |
2.2.6. Arrangement of cabin balconies
Non-load bearing partial bulkheads which separate adjacent cabin balconies shall be capable of being opened by the crew from each side for the purpose of fighting fires.
2.2.7. Protection of atriums
| 2.2.7.1. | Atriums shall be within enclosures formed of ‘A’ class divisions having a fire rating determined in accordance with tables 9.2 and 9.4, as applicable. | |
| --- | --- | --- |
| 2.2.7.2. | Decks separating spaces within atriums shall have a fire rating determined in accordance with tables 9.2 and 9.4, as applicable. |
3. Penetrations in fire-resisting divisions and prevention of heat transmission
| 3.1. | Where class ‘A’ divisions are penetrated for the passage of electric cables, pipes, trunks, ducts etc., or for girders, beams or other structural members, such penetrations shall be tested in accordance with the Fire Test Procedures Code to ensure that the fire resistance of the divisions is not impaired. In the case of ventilation ducts, paragraphs 7.1.2 and 7.3.1 apply. However, where a pipe penetration is made of steel or equivalent material having a thickness of 3 mm or greater and a length of not less than 900 mm (preferably 450 mm on each side of the division) and no openings, testing is not required. Such penetrations shall be suitably insulated by extension of the insulation at the same level of the division. | |
| --- | --- | --- |
| 3.2. | Where class ‘B’ divisions are penetrated for the passage of electric cables, pipes, trunks, ducts etc., or for the fitting of ventilation terminals, lighting fixtures and similar devises, arrangements shall be made to ensure that the fire resistance of the divisions is not impaired, subject to the provisions of paragraph 7.3.2. Pipes other than steel or copper that penetrate ‘B’ class divisions shall be protected by either: .1 a fire tested penetration device, suitable for the fire resistance of the division pierced and the type of the pipe used; or .2 a steel sleeve, having a thickness of not less than 1,8 mm and a length of not less than 900 mm for pipe diameters of 150 mm or more and not less than 600 mm for pipe diameters of less than 150 mm (preferably equally divided to each side of the division). The pipe shall be connected to the ends of the sleeve by flanges or couplings or the clearance between the sleeve and the pipe shall not exceed 2,5 mm or any clearance between pipe and sleeve shall be made tight by means of non-combustible or other suitable material. | |
| --- | --- | --- |
| 3.3. | No-insulated metallic pipes penetrating ‘A’ or ‘B’ class divisions shall be of materials having a melting temperature which exceeds 950 °C for ‘A-0’ and 850 °C for ‘B-0’ class divisions. | |
| --- | --- | --- |
| 3.4. | In approving structural fire protection details the Administration of the flag State shall have regard to the risk of heat transmission at intersections and terminal points of required thermal barriers. In the implementation of fire proofing measures, steps shall be undertaken by the Administration of the flag State to prevent heat transfer through heat bridges, e.g. between decks and bulkheads. The insulation of a deck or bulkhead shall be carried past the penetration, intersection or terminal point for a distance of at least 450 mm in the case of steel and aluminium structures. If a space is divided with a deck or a bulkhead of ‘A’ class standard having insulation of different values, the insulation with the higher value shall continue on the deck or bulkhead with the insulation of the lesser value for a distance of at least 450 mm. |
4. Protection of openings in fire-resisting divisions
4.1.1. Penetrations and openings in ‘A’ class divisions
| 4.1.1.1. | All openings in ‘A’ class divisions shall be provided with permanently attached means of closing which shall be as effective for resisting fires as the divisions in which they are fitted. | |
| --- | --- | --- |
| 4.1.1.2. | The construction of all doors and door frames in ‘A’ class divisions, with the means of securing them when closed, shall provide resistance to fire as well as to the passage of smoke and flame, as far as practicable, equivalent to that of the bulkheads in which the doors are situated. Such doors and doorframes shall be constructed of steel or other equivalent material. | |
| --- | --- | --- |
| 4.1.1.3. | Watertight doors need not be insulated. | |
| --- | --- | --- |
| 4.1.1.4. | It shall be possible for each door to be opened and closed from each side of the bulkhead by one person only. | |
| --- | --- | --- |
| 4.1.1.5. | Fire doors in main vertical zone bulkheads, galley boundaries and stairway enclosures other than power-operated watertight doors and those which are normally locked, shall satisfy the following requirements: .1 the doors shall be self-closing and be capable of closing against an angle of inclination of up to 3,5° opposing closure; .2 the approximate time of closure for hinged fire doors shall be no more than 40 seconds and no less than 10 seconds from the beginning of their movement with the ship in upright position. The approximate uniform rate of closure for sliding fire doors shall be of no more than 0,2 m/s and no less than 0,1 m/s with the ship in the upright position; .3 the doors shall be capable of remote release from the continuously manned central control station, either simultaneously or in groups and shall be capable of release also individually from a position at both sides of the door. Release switches shall have an on-off function to prevent automatic resetting of the system; .4 hold-back hooks not subject to central control station release are prohibited; .5 a door closed remotely from the central control station shall be capable of being reopened at both sides of the door by local control. After such local opening, the door shall automatically close again; .6 indication shall be provided at the fire door indicator panel in the continuously manned central control station whether each of the remote-released doors are closed; .7 the release mechanism shall be so designed that the door will automatically close in the event of disruption of the control system or main source of electric power; .8 local power accumulators for power-operated doors shall be provided in the immediate vicinity of the doors to enable the doors to be operated after disruption of the control system or main source of electric power at least 10 times (fully opened or closed) using the local controls; .9 disruption of the control system or main source of electric power at one door shall not impair the safe functioning of the other doors; .10 remote-released sliding or power-operated doors shall be equipped with an alarm that sounds for at least 5 seconds but no more than 10 seconds after the door is released from the central control station and before the door begins to move and continue sounding until the door is completely closed; .11 a door designed to re-open upon contacting an object in its path shall re-open not more than 1 metre from the point of contact; .12 double-leaf doors equipped with latch necessary to their fire integrity shall have a latch that is automatically activated by the operation of the doors when released by the control system; .13 doors giving direct access to special category spaces which are power-operated and automatically closed need not be equipped with the alarms and remote-release mechanisms required in paragraph.3 and.10; .14 the components of the local control system shall be accessible for maintenance and adjusting; and .15 power-operated doors shall be provided with a control system of an approved type which shall be able to operate in case of fire, this being determined in accordance with the Fire Test Procedure Code. This system shall satisfy the following requirements: .1 the control system shall be able to operate the door at a temperature of at least 200 °C for at least 60 minutes, served by the power supply; .2 the power supply for all other doors not subject to fire shall not be impaired, and; .3 at temperatures exceeding 200 °C the control system shall be automatically isolated from the power supply and shall be capable of keeping the door closed up to at least 945 °C. | |
| --- | --- | --- |
| 4.1.1.7. | The requirements for ‘A’ class integrity of the outer boundaries of a ship shall not apply to glass partitions, windows and sidescuttles, provided that there is no requirement for such boundaries to have a ‘A’ class integrity in paragraphs 4.1.3.5 and 4.1.3.6. The requirements for ‘A’ class integrity of the outer boundaries of the ship shall not apply to exterior doors, except for those in superstructures and deckhouses facing life-saving appliances, embarkation and external assembly station areas, external stairs and open decks used for escape routes. Stairway enclosure doors need not meet this requirement. | |
| --- | --- | --- |
| 4.1.1.8. | Except for watertight doors, weathertight doors (semi-watertight doors), doors leading to the open deck and doors which need to be reasonably gastight, all ‘A’ class doors located in stairways, public spaces and main vertical zone bulkheads in escape routes shall be equipped with a self-closing hose port of material, construction and fire resistance which is equivalent to the door into which it is fitted, and shall be a 150 mm square clear opening with the door closed and shall be inset into the lower edge of the door, opposite to the door hinges or, in the case of sliding doors, nearest the opening. |
4.1.2. Penetrations and openings in ‘B’ class divisions
| 4.1.2.1. | Doors and door frames in ‘B’ class divisions and means of securing them shall provide a method of closure which shall have resistance to fire equivalent to that of the divisions except that ventilation openings may be permitted in the lower portion of such doors. Where such opening is in or under a door, the total net area of any such opening or openings shall not exceed 0,05 m2. Alternatively, a non-combustible air balance duct routed between the cabin and the corridor and located below the sanitary unit is permitted where the cross-sectional area of the duct does not exceed 0,05 m2. All ventilation openings shall be fitted with a grill made of non-combustible material. Doors shall be non-combustible. | |
| --- | --- | --- |
| 4.1.2.1a | For reasons of noise reduction, the Administration may approve, as an equivalent, doors with built-in ventilation sound-locks with openings at the bottom on one side of the door and at the top on the other side, on condition that the following provisions have been complied with: .1 The upper opening shall always face towards the corridor and shall be provided with a grating of non-combustible material and an automatically operating fire damper, which is activated at a temperature of about 70 °C. .2 The lower opening shall be provided with a grating made of a non-combustible material. .3 The doors shall be tested in accordance with the Fire Test Procedures Code. | |
| --- | --- | --- |
| 4.1.2.2. | Cabin doors in ‘B’ class divisions shall be of a self-closing type. Hold-backs are not permitted. | |
| --- | --- | --- |
| 4.1.2.3. | The requirements for ‘B’ class integrity of the outer boundaries of a ship shall not apply to glass partitions, windows and sidescuttles. Similarly, the requirements for ‘B’ class integrity shall not apply to exterior doors in superstructures and deckhouses. For ships carrying not more than 36 passengers, the Administration of the flag State may permit the use of combustible materials in doors separating cabins from the individual interior sanitary spaces such as showers. |
4.1.3. Windows and sidescuttles
| 4.1.3.1. | All windows and sidescuttles in bulkheads within accommodation and service spaces and control stations other than those to which the provisions of paragraphs 4.1.1.7 and 4.1.2.3 apply, shall be so constructed as to preserve the integrity requirements of the type of bulkheads in which they are fitted, this being determined in accordance with the Fire Test Procedures Code. | |
| --- | --- | --- |
| 4.1.3.2. | Notwithstanding the requirements of the tables 9.1 to 9.4, all windows and sidescuttles in bulkheads separating accommodation and service spaces and control stations from weather shall be constructed with frames of steel or other suitable material. The glass shall be retained by a metal glazing bead or angle. | |
| --- | --- | --- |
| 4.1.3.5. | For ships carrying more than 36 passengers, windows facing survival craft, embarkation and assembly stations, external stairs and open decks used for escape routes, and windows situated below liferaft and escape slide embarkation areas shall have fire integrity as required in table 9.1. Where automatic dedicated sprinkler heads are provided for windows, "A-0" windows may be accepted as equivalent. To be considered under this paragraph, the sprinkler heads must either be: .1 dedicated heads located above the windows, and installed in addition to the conventional ceiling sprinklers; or .2 conventional ceiling sprinkler heads arranged such that the window is protected by an average application rate of at least 5 l/min per square metre and the additional window area is included in the calculation of the area of coverage; or .3 water-mist nozzles that have been tested and approved in accordance with the ‘Revised guidelines for approval of sprinkler systems equivalent to that referred to in SOLAS Regulation II-2/12 (resolution A.800(19), as amended).’; and Windows located in the ship’s side below the lifeboat embarkation area shall have fire integrity at least equal to ‘A-0’ class. | |
| --- | --- | --- |
| 4.1.3.6. | For ships carrying not more than 36 passengers, windows facing survival craft and escape slide, embarkation areas and windows situated below such areas shall have fire integrity at least equal to ‘A-0’ class. |
5. Protection of openings in machinery spaces boundaries
| 5.2.1. | The number of skylights, doors, ventilators, openings in funnels to permit exhaust ventilation and other openings to machinery spaces shall be reduced to a minimum consistent with the needs of ventilation and the proper and safe working of the ship. | |
| --- | --- | --- |
| 5.2.2. | Skylights shall be of steel or equivalent material and shall not contain glass panels. | |
| --- | --- | --- |
| 5.2.3. | Means of control shall be provided for closing power-operated doors or actuating release mechanism on doors other than power-operated watertight doors. The controls shall be located outside the space concerned, where they will not be cut off in the event of fire in the space they serve. | |
| --- | --- | --- |
| 5.2.4. | The means of control required in paragraph 5.2.3 shall be situated at one control position or grouped in as few positions as possible. Such positions shall have a safe access from the open deck. | |
| --- | --- | --- |
| 5.2.5. | Doors other than power-operated watertight doors, shall be so arranged that positive closure is assured in case of fire in the space, by power-operated closing arrangements or by the provision of self-closing doors capable of closing against an inclination of 3,5° opposing closure and having a fail-safe hold-back facility, provided with a remotely operated release device. | |
| --- | --- | --- |
| 5.2.6. | Windows shall not be fitted in machinery space boundaries. This does not preclude the use of glass in control rooms within the machinery spaces. |
6. Protection of cargo space boundaries
| 6.2. | Indicators shall be provided on the navigating bridge which shall indicate when any fire door leading to or from the special category spaces is closed. Doors to special category spaces shall be of such a construction that they cannot be kept open permanently and shall be kept closed during the voyage. |
7. Ventilation systems
7.1. General
- 7.1.1. Ventilation ducts, including single and double wall ducts, shall be of steel or an equivalent material, except for flexible bellows of short length not exceeding 600 mm used for connecting fans to the ducting in air-conditioning rooms. Unless expressly provided otherwise in paragraph 7.1.6, any other material used in the construction of ducts, including insulation, shall also be non-combustible. However, short ducts, not exceeding 2 m in length and with a free cross-sectional area (The term free cross-sectional area means, even in the case of a pre-insulated duct, the area calculated on the basis of the inner dimensions of the duct itself and not the insulation) not exceeding 0.02 m2, need not be of steel or equivalent material, subject to the following conditions:
- .1 the ducts shall be made of non-combustible material which may be faced internally and externally with membranes having low flame-spread characteristics and, in each case, a calorific value not exceeding 45 MJ/m2 of their surface area for the thickness used. The calorific value shall be calculated in accordance with the recommendations published by the International Organization for Standardization, in particular publication ISO 1716:2002, ‘Reaction to the fire tests for building products – Determination of the heat of combustion’;
- .2 the ducts are only used at the end of the ventilation device; and
- .3 the ducts are not situated less than 600 mm, measured along the duct, from an opening in an ‘A’ or ‘B’ class division, including continuous ‘B’ class ceiling.
- 7.1.2. The following arrangements shall be tested in accordance with the Fire Test Procedures Code:
- .1 fire dampers, including their relevant means of operation, although the testing is not required for dampers located at the lower end of the duct in exhaust ducts for galley ranges, which must be of steel and capable of stopping the draught in the duct; and
- .2 duct penetrations through ‘A’ class divisions, although the testing is not required where steel sleeves are directly joined to ventilation ducts by means of riveted or screwed connections or by welding.
- 7.1.3. Fire dampers shall be easily accessible. Where they are placed behind ceilings or linings, those ceilings or linings shall be provided with an inspection hatch on which the identification number of the fire damper is marked. The fire damper identification number shall also be marked on any remote controls provided.
- 7.1.4. Ventilation ducts shall be provided with hatches for inspection and cleaning. The hatches shall be located near the fire dampers.
- 7.1.5. The main inlets and outlets of ventilation systems shall be capable of being closed from outside the spaces being ventilated. The means of closing shall be easily accessible as well as prominently and permanently marked and shall indicate the operating position of the closing device.
- 7.1.6. Combustible gaskets in flanged ventilation duct connections are not permitted within 600 mm of openings in ‘A’ or ‘B’ class divisions and in ducts required to be of ‘A’ class construction.
- 7.1.7. Ventilation openings or air balance ducts between two enclosed spaces shall not be provided except as permitted by paragraph 4.1.2.1.
7.2. Arrangement of ducts
- 7.2.1. The ventilation systems for machinery spaces of category A, ro-ro cargo spaces, galleys, special category spaces and cargo spaces shall be separated from each other and from the ventilation systems serving other spaces. However, the galley ventilation systems in ships carrying not more than 36 passengers need not be completely separated from other ventilation systems, but may be served by separate ducts from a ventilation unit serving other spaces. In such a case, an automatic fire damper shall be fitted in the galley ventilation duct near the ventilation unit.
- 7.2.2. Ducts provided for the ventilation of machinery spaces of category A, galleys, ro-ro cargo spaces or special category spaces shall not pass through accommodation spaces, service spaces, or control stations unless they comply with paragraph 7.2.4.
- 7.2.3. Ducts provided for the ventilation of accommodation spaces, service spaces or control stations shall not pass through machinery spaces of category A, galleys, ro-ro cargo spaces or special category spaces unless they comply with paragraph 7.2.4.
- 7.2.4. As permitted by paragraphs 7.2.2 and 7.2.3 ducts shall be either:
- .1.1 constructed of steel having a thickness of at least 3 mm for ducts with a free cross-sectional area of less than 0.075 m2, at least 4 mm for ducts with a free cross-sectional area of between 0.075 m2 and 0.45 m2, and at least 5 mm for ducts with a free cross-sectional area of over 0.45 m2;
- .1.2 suitably supported and stiffened;
- .1.3 fitted with automatic fire dampers close to the boundaries penetrated; and
- .1.4 insulated to ‘A-60’ class standard from the boundaries of the spaces they serve to a point at least 5 m beyond each fire damper;
or
- .2.1 constructed of steel in accordance with paragraphs 7.2.4.1.1 and 7.2.4.1.2; and
- .2.2 insulated to ‘A-60’ class standard throughout the spaces they pass through, except for ducts that pass through spaces of category (9) or (10) as defined in paragraph 2.2.3.2.2.
- 7.2.5. For the purposes of paragraphs 7.2.4.1.4 and 7.2.4.2.2, ducts shall be insulated over their entire cross-sectional external surface. Ducts that are outside but adjacent to the specified space, and share one or more surfaces with it, shall be considered to pass through the specified space and shall be insulated over the surface they share with the space for a distance of 450 mm past the duct (Sketches of such arrangements are contained in the Unified Interpretations of SOLAS chapter II-2 (MSC.1/Circ.1276)).
- 7.2.6. Where it is necessary that a ventilation duct passes through a main vertical zone division, an automatic fire damper shall be fitted adjacent to the division. The damper shall also be capable of being manually closed from each side of the division. The control location shall be readily accessible and be clearly and prominently marked. The duct between the division and the damper shall be constructed of steel in accordance with paragraphs 7.2.4.1.1 and 7.2.4.1.2 and insulated to at least the same fire integrity as the division penetrated. The damper shall be fitted on at least one side of the division with a visible indicator showing the operating position of the damper.
7.3. Details of fire dampers and duct penetrations
- 7.3.1. Ducts passing through ‘A’ class divisions shall meet the following requirements:
- .1 where a thin plated duct with a free cross sectional area equal to, or less than, 0.02 m2 passes through ‘A’ class divisions, the opening shall be fitted with a steel or equivalent material sheet sleeve having a thickness of at least 3 mm and a length of at least 200 mm, divided preferably into 100 mm on each side of a bulkhead or, in the case of a deck, wholly laid on the lower side of the decks penetrated. These sleeves lining such ducts, if not made of steel, shall be provided with fire insulation. The insulation shall have at least the same fire integrity as the division through which the duct passes;
- .2 where ventilation ducts with a free cross-sectional area exceeding 0.02 m2, but not more than 0.075 m2, pass through ‘A’ class divisions, the openings shall be lined with steel or equivalent material sheet sleeves. The ducts and sleeves shall have a thickness of at least 3 mm and a length of at least 900 mm. When passing through bulkheads, this length shall be divided preferably into 450 mm on each side of the bulkhead. These ducts, or sleeves lining such ducts, shall be provided with fire insulation. The insulation shall have at least the same fire integrity as the division through which the duct passes; and
- .3 automatic fire dampers shall be fitted in all ducts with a free cross-sectional area exceeding 0.075 m2 that pass through ‘A’ class divisions. Each damper shall be fitted close to the division penetrated and the duct between the damper and the division penetrated shall be constructed of steel in accordance with paragraphs 7.2.4.2.1 and 7.2.4.2.2. The fire damper shall operate automatically, but shall also be capable of being closed manually from both sides of the division. The damper shall be fitted with a visible indicator which shows the operating position of the damper. Fire dampers are not required, however, where ducts pass through spaces surrounded by ‘A’ class divisions, without serving those spaces, provided those ducts have the same fire integrity as the divisions which they penetrate. A duct of cross-sectional area exceeding 0.075 m2 shall not be divided into smaller ducts at the penetration of an ‘A’ class division and then recombined into the original duct once through the division to avoid installing the damper required by this provision.
- 7.3.2. Ventilation ducts with a free cross-sectional area exceeding 0.02 m2 passing through ‘B’ class bulkheads shall be lined with steel or equivalent material sheet sleeves of 900 mm in length, divided preferably into 450 mm on each side of the bulkheads unless the duct is of steel for this length. These sleeves lining such ducts, if not made of steel, shall be provided with fire insulation. The insulation shall have at least the same fire integrity as the division through which the duct passes.
- 7.3.3. All fire dampers shall be capable of manual operation. The dampers shall have a direct mechanical means of release or, alternatively, be closed by electrical, hydraulic, or pneumatic operation. All dampers shall be manually operable from both sides of the division. Automatic fire dampers, including those capable of remote operation, shall have a failsafe mechanism that will close the damper in a fire even upon loss of electrical power or hydraulic or pneumatic pressure loss. Remotely operated fire dampers shall be capable of being reopened manually at the damper.
7.4. Ventilation systems for ships carrying more than 36 passengers
- 7.4.1. In addition to the requirements in sections 7.1, 7.2 and 7.3, the ventilation system of a passenger ship carrying more than 36 passengers shall also meet the following requirements.
- 7.4.2. In general, the ventilation fans shall be so arranged that the ducts reaching the various spaces remain within a main vertical zone.
- 7.4.3. Stairway enclosures shall be served by an independent ventilation fan and duct system (exhaust and supply) which shall not serve any other spaces in the ventilation systems.
- 7.4.4. A duct, irrespective of its cross-section, serving more than one ‘tween-deck accommodation space, service space or control station, shall be fitted, near the penetration of each deck of such spaces, with an automatic smoke damper that shall also be capable of being closed manually from the protected deck above the damper. Where a fan serves more than one ‘tween-deck’ space through separate ducts within a main vertical zone, whereby each one is dedicated to a single ‘tween-deck space, each duct shall be provided with a manually operated smoke damper fitted close to the fan.
- 7.4.5. Vertical ducts shall, where necessary, be insulated as required by tables 9.1 and 9.2. Ducts shall be insulated as required for decks between the space they serve and the space being considered, as applicable.
7.5. Exhaust ducts from galley ranges
7.5.1. Requirements for ships carrying more than 36 passengers
- 7.5.1.1 In addition to the requirements in sections 7.1, 7.2 and 7.3, exhaust ducts from galley ranges shall be constructed in accordance with paragraphs 7.2.4.2.1 and 7.2.4.2.2 and insulated to ‘A-60’ class standard throughout accommodation spaces, service spaces, or control stations they pass through. They shall also be fitted with:
- .1 a grease trap readily removable for cleaning unless an alternative approved grease removal system is fitted;
- .2 a fire damper located in the lower end of the duct at the junction between the duct and the galley range hood which is automatically and remotely operated and, in addition, a remotely operated fire damper located in the upper end of the duct close to the outlet of the duct;
- .3 a fixed means for extinguishing a fire within the duct. The fire extinguishing systems shall comply with the recommendations published by the International Organization for Standardization, in particular publication ISO 15371:2009 ‘Ships and marine technology – Fire-extinguishing systems for protection of galley cooking equipment’;
- .4 remote-control arrangements for shutting off the exhaust fans and supply fans, for operating the fire dampers mentioned in paragraph 7.5.1.1.2 and for operating the fire-extinguishing system, which shall be placed in a position outside the galley close to the entrance to the galley. Where a multi-branch system is installed, a remote means located with the above controls shall be provided to close all branches exhausting through the same main duct before an extinguishing medium is released into the system; and
- .5 suitably located hatches for inspection and cleaning, including one provided close to the exhaust fan and one fitted in the lower end where grease accumulates.
- 7.5.1.2 Exhaust ducts from ranges for cooking equipment installed on open decks shall conform to paragraph 7.5.1.1, as applicable, when passing through accommodation spaces or spaces containing combustible materials.
7.5.2. Requirements for ships carrying not more than 36 passengers
When passing through accommodation spaces or spaces containing combustible materials, the exhaust ducts from galley ranges shall be constructed in accordance with paragraphs 7.2.4.1.1 and 7.2.4.1.2. Each exhaust duct shall be fitted with:
- .1 a grease trap readily removable for cleaning;
- .2 an automatically and remotely operated fire damper located in the lower end of the duct at the junction between the duct and the galley range hood and, in addition, a remotely operated fire damper in the upper end of the duct close to the outlet of the duct;
- .3 arrangements, operable from within the galley, for shutting off the exhaust and supply fans; and
- .4 fixed means for extinguishing a fire within the duct. The fire extinguishing systems shall comply with the recommendations published by the International Organization for Standardization, in particular publication ISO 15371:2009 ‘Ships and marine technology – Fire-extinguishing systems for protection of galley cooking equipment’.
7.6. Ventilation rooms serving machinery spaces of category A containing internal combustion machinery
- 7.6.1. Where a ventilation room serves only such an adjacent machinery space and there is no fire division between the ventilation room and the machinery space, the means for closing the ventilation duct or ducts serving the machinery space shall be located outside of the ventilation room and machinery space.
- 7.6.2. Where a ventilation room serves such a machinery space as well as other spaces and is separated from the machinery space by a ‘A-0" class division, including penetrations, the means for closing the ventilation duct or ducts for the machinery space can be located in the ventilation room.
7.7. Ventilation systems for laundries in ships carrying more than 36 passengers
Exhaust ducts from laundries and drying rooms of category (13) spaces as defined in paragraph 2.2.3.2.2 shall be fitted with:
- .1 filters readily removable for cleaning purposes;
- .2 a fire damper located in the lower end of the duct which is automatically and remotely operated;
- .3 remote-control arrangements for shutting off the exhaust fans and supply fans from within the space and for operating the fire damper mentioned in paragraph 7.7.2; and
- .4 suitably located hatches for inspection and cleaning.
Regulation II-2/C/10: Fire fighting
1. Purpose
| 1.1. | The purpose of this Regulation II-2/C/10 is to suppress and swiftly extinguish a fire in the space of origin. For this purpose, the following functional requirements shall be met: .1 fixed fire-extinguishing systems shall be installed having due regard to the fire growth potential of the protected spaces; and .2 fire-extinguishing appliances shall be readily available. |
2. Water supply systems
Every ship shall be provided with fire pumps, fire mains, hydrants, hoses and nozzles complying as applicable with the requirements of this Regulation II-2/C/10.
Reading this document does not replace reading the official text published in the Official Journal of the European Union. We assume no responsibility for any inaccuracies arising from the conversion of the original to this format.
This text is published under EUR-Lex's own terms of reuse, not a Legalize or public-domain licence.
EUR-Lex
Creative Commons Attribution 4.0 International (CC BY 4.0)
© European Union, https://eur-lex.europa.eu — Source: EUR-Lex (Publications Office of the European Union). Reused under the Creative Commons Attribution 4.0 International (CC BY 4.0) licence. Only EU legislation published in the printed Official Journal of the European Union is deemed authentic; consolidated texts are reproduced here for documentation purposes and have been reformatted to Markdown.